Survey Date: Thursday, July 24, 2014
Survey Type: Health
Deficiency: F0241 (Provide care for residents in a way that maintains or improves their dignity and respect in full rec)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, August 5, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a complaint inspection)
Survey Date: Thursday, July 24, 2014
Survey Type: Health
Deficiency: F0490 (Make sure that the facility is administered in an acceptable way that maintains the well-being of ea)
Scope Severity Code: K
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, August 5, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a complaint inspection)
Survey Date: Thursday, July 24, 2014
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: K
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, August 5, 2014
The inspection cycle of deficiency: 1 (the deficiency was found on a complaint inspection)
Survey Date: Wednesday, July 10, 2013
Survey Type: Fire Safety
Deficiency: K0064 (Portable fire extinguishers.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, July 26, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 10, 2013
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, August 23, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 10, 2013
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 19, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 10, 2013
Survey Type: Fire Safety
Deficiency: K0052 (An approved installation, maintenance and testing program for fire alarm systems.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, August 12, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 10, 2013
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, July 24, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Wednesday, July 10, 2013
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, July 15, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 17, 2012
Survey Type: Health
Deficiency: F0246 (Reasonably accommodate the needs and preferences of each resident.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 1, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 17, 2012
Survey Type: Health
Deficiency: F0282 (Provide care by qualified persons according to each resident's written plan of care.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 1, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Thursday, May 17, 2012
Survey Type: Health
Deficiency: F0441 (Have a program that investigates, controls and keeps infection from spreading.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, July 1, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 23, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0025 (Walls that prevent smoke from passing through and would resist fire for at least one hour.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 21, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0052 (An approved installation, maintenance and testing program for fire alarm systems.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, June 11, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0066 (Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, June 13, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 8, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Wednesday, May 16, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 28, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 21, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0072 (Exits that are free from obstructions and can be used at all times.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, June 24, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0022 (Signs that state that exit doors are to be kept closed.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, June 29, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, May 15, 2012
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, June 21, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)
Survey Date: Tuesday, November 1, 2011
Survey Type: Health
Deficiency: F0202 (Provide written records when a resident is transferred or discharged.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, November 29, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Tuesday, November 1, 2011
Survey Type: Health
Deficiency: F0203 (Provide timely notification to the resident before transfer or discharge.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, November 29, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Tuesday, November 1, 2011
Survey Type: Health
Deficiency: F0177 (Protect a residents' right to refuse some types of non-requested transfers within the nursing home.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, November 29, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0412 (Provide or obtain dental services for each resident.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0520 (Set up an ongoing quality assessment and assurance group to review quality deficiencies quarterly, a)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0248 (Provide activities to meet the interests and needs of each resident.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0280 (Allow residents the right to participate in the planning or revision of care and treatment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0272 (Conduct initial and periodic assessments of each resident's functional capacity.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0490 (Make sure that the facility is administered in an acceptable way that maintains the well-being of ea)
Scope Severity Code: K
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0356 (Post nurse staffing information/data on a daily basis.)
Scope Severity Code: B
Deficiency Corrected: Deficient, Provider Has No Plan Of Correction
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0282 (Provide care by qualified persons according to each resident's written plan of care.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0279 (Develop a complete care plan that meets all the resident's needs, with timetables and actions that c)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0312 (Assist those residents who need help with eating/drinking, grooming and personal and oral hygiene.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)
Survey Date: Friday, April 15, 2011
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: K
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, May 17, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)