Gateway Care And Retirement

Gateway Care And Retirement was recognized and ceritified in 2003 by Centers for Medicare & Medicaid Services as one of model nursing home providers promoting health and improving quality of life. Gateway Care And Retirement which is located in 39 Ne 102Nd Avenue Portland, is scientifically measured and assessed by Centers for Medicare & Medicaid Services and is shown to provide good nursing home services or products under the Medicare program. Gateway Care And Retirement is being offered ceritified services and products in Oregon.
Address:   39 Ne 102Nd Avenue
       Portland, OR 97220

Phone:   (503) 252-2461

County: Multnomah
Federal Provider Number: 385268
Participates in: Medicare And Medicaid
Certified Date: Monday, September 1, 2003 (21 years certified)
Certified Agency: Centers for Medicare & Medicaid Services
Legal Business Name: Gateway, Inc.
Ownership Type: For Profit - Corporation
Provider Changed Ownership in Last 12 Months: No



TypeNameRole Description
PersonCarolyn Werner5% Or More Ownership Interest
PersonAuthur WernerDirector/officer
PersonAuthur Werner5% Or More Ownership Interest
PersonAllen JamesW-2 Managing Employee

Provider Resides in Hospital: No
Number of Federally Certified Beds: 59
Number of Residents in Federally Certified Beds: 50 (85% occupied)
Continuing Care Retirement Community: No
Special Focus Facility: No
With a Resident and Family Council: Both
Automatic Sprinkler Systems in All Required Areas: Yes


Survey Date: Monday, November 4, 2013
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 21, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a complaint inspection)

Survey Date: Wednesday, September 4, 2013
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, September 27, 2013
The inspection cycle of deficiency: 1 (the deficiency was found on a standard inspection)

Survey Date: Tuesday, August 6, 2013
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Sunday, August 25, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)

Survey Date: Friday, January 11, 2013
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, February 22, 2013
The inspection cycle of deficiency: 2 (the deficiency was found on a complaint inspection)

Survey Date: Thursday, September 20, 2012
Survey Type: Health
Deficiency: F0323 (Ensure that a nursing home area is free from accident hazards and provide adequate supervision to pr)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, November 8, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)

Survey Date: Thursday, April 26, 2012
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, June 12, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)

Survey Date: Thursday, April 26, 2012
Survey Type: Health
Deficiency: F0281 (Ensure services provided by the nursing facility meet professional standards of quality.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Tuesday, June 12, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)

Survey Date: Monday, April 23, 2012
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Thursday, May 10, 2012
The inspection cycle of deficiency: 2 (the deficiency was found on a standard inspection)

Survey Date: Wednesday, December 7, 2011
Survey Type: Health
Deficiency: F0281 (Ensure services provided by the nursing facility meet professional standards of quality.)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, January 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)

Survey Date: Wednesday, December 7, 2011
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: G
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Monday, January 23, 2012
The inspection cycle of deficiency: 3 (the deficiency was found on a complaint inspection)

Survey Date: Thursday, March 3, 2011
Survey Type: Health
Deficiency: F0272 (Conduct initial and periodic assessments of each resident's functional capacity.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, May 6, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Thursday, March 3, 2011
Survey Type: Health
Deficiency: F0279 (Develop a complete care plan that meets all the resident's needs, with timetables and actions that c)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, May 6, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Thursday, March 3, 2011
Survey Type: Health
Deficiency: F0278 (Ensure each resident receives an accurate assessment by a qualified health professional.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, May 6, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Thursday, March 3, 2011
Survey Type: Health
Deficiency: F0309 (Provide necessary care and services to maintain or improve the highest well being of each resident .)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, May 6, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Thursday, March 3, 2011
Survey Type: Health
Deficiency: F0503 (Ensure laboratory services, blood blanks and transfusion services provided on site meet requirements)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, May 6, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0048 (A written emergency evacuation plan.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0144 (Weekly inspections and monthly testing of generators.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0064 (Portable fire extinguishers.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0017 (Corridors that are separated from use areas by walls constructed to limit the passage of smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0047 (Properly located and lighted "Exit" signs.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0073 (Restrictions on the use of highly flammable decorations.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0211 (Properly installed hallway dispensers for alcohol-based hand rub.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0018 (Corridor and hallway doors that block smoke.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0050 (Record of quarterly fire drills for each shift under varying conditions.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0038 (Exits that are accessible at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0056 (An approved automatic sprinkler system connected to the fire alarm system.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0076 (Proper medical gas storage and administration areas.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0130 (Other fire safety features required by fire safety codes.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0069 (Properly protected cooking facilities.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0052 (An approved installation, maintenance and testing program for fire alarm systems.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0062 (Automatic sprinkler systems that have been maintained in working order.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0011 (A two-hour-resistant firewall separation.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0045 (Proper backup exit lighting.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0072 (Exits that are free from obstructions and can be used at all times.)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0029 (Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishi)
Scope Severity Code: E
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0147 (Properly installed electrical wiring and equipment.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0066 (Posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0012 (Approved construction type or materials.)
Scope Severity Code: F
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Survey Date: Friday, February 25, 2011
Survey Type: Fire Safety
Deficiency: K0039 (Corridors or aisles that are unobstructed and are at least 8 feet in width.)
Scope Severity Code: D
Deficiency Corrected: Deficient, Provider Has Date Of Correction
Date the deficiency was corrected: Friday, April 22, 2011
The inspection cycle of deficiency: 3 (the deficiency was found on a standard inspection)

Number of Facility Reported Incidents: 3
Number of Substantiated Complaints: 2
Number of Fines: 1
Number of Payment Denials: 0
Total Number of Penalties: 1
Total Amount of Fines in Dollars: USD 975


Date of inspection that triggered the penalty: Wednesday, December 7, 2011
Penalty Type: Fine
Fine Amount: 975
This data allows consumers to compare information about nursing homes. Information here is not an endorsement or advertisement for any nursing home and should be considered carefully. Use it with other information you gather about nursing homes facilities. Talk to your doctor or other health care provider about this.



This data was updated by using data source from Centers for Medicare and Medicaid Services (CMS) which is publicized on Wednesday, October 1, 2014. If you found out that something incorrect and want to change it, please follow this Update Data guide.

The Five Star Quality Rating System is not a substitute for visiting the nursing home. This system can give you important information, help you compare nursing homes by topics you consider most important, and help you think of questions to ask when you visit the nursing home. Use the Five-Star ratings together with other sources of information.

items rating
Health Inspection Rating (4 out of 5 stars)
Quality Rating (4 out of 5 stars)
Staffing Rating (5 out of 5 stars)
RN Staffing Rating (5 out of 5 stars)
Overall Rating (5 out of 5 stars)
Nursing homes vary in the quality of care and services they provide to their residents. Reviewing health inspection results, staffing data, and quality measure data are three important ways to measure nursing home quality. This information gives you a "snap shot" of the care individual nursing home give.


Patients experiences Provider State Nation
Percent of High Risk Long Stay Residents With Pressure Ulcers
N/A
6%
6%
Percent of Long Stay Residents Experiencing One or More Falls with Major Injury
N/A
3%
3%
Percent of Long Stay Residents Who Self Report Moderate to Severe Pain
N/A
12%
8%
Percent of Long Stay Residents Who Were Physically Restrained
N/A
1%
1%
Percent of Long Stay Residents Whose Need for Help with ADLs has Increased
N/A
13%
16%
Percent of Long Stay Residents with a Catheter Inserted and Left in Their Bladder
N/A
5%
3%
Percent of Long Stay Residents With a Urinary Tract Infection
N/A
6%
6%
Percent of Short Stay Residents Who Self Report Moderate to Severe Pain
N/A
24%
19%
Percent of Short Stay Residents With Pressure Ulcers That Are New or Worsened
N/A
1%
1%
Percent of Long Stay Residents Assessed and Appropriately Given the Pneumococcal Vaccine
N/A
93%
94%
Percent of Long Stay Residents Assessed and Appropriately Given the Seasonal Influenza Vaccine
N/A
92%
94%
Percent of Long Stay Residents Who Have Depressive Symptoms
N/A
5%
6%
Percent of Long Stay Residents Who Lose Too Much Weight
N/A
8%
7%
Percent of Long Stay Residents Who Received an Antipsychotic Medication
N/A
18%
20%
Percent of Low Risk Long Stay Residents Who Lose Control of Their Bowel or Bladder
N/A
49%
44%
Percent of Short Stay Residents Assessed and Appropriately Given the Pneumococcal Vaccine
N/A
82%
83%
Percent of Short Stay Residents Who Newly Received an Antipsychotic Medication
N/A
2%
2%
Percent of Short Stay Residents Who Were Assessed and Appropriately Given the Seasonal Influenza Vaccine
N/A
84%
84%

N/A
Data not available.

See more related providers



Reviews

Gateway Care And Retirement [Federal No:385268] near 39 Ne 102Nd Avenue, Portland OR

Most visited providers

Top rated Medicare providers